SolarMax
6MT2 |
SolarMax
8MT2 |
SolarMax
10MT2 |
SolarMax
13MT2 |
SolarMax
15MT2 |
SolarMax
13MT3 |
SolarMax
15MT3 |
Цени |
Запитване |
Запитване |
Запитване |
Запитване |
Запитване |
Запитване |
Запитване |
Input values |
MPP voltage range 1) |
340 V..750V |
300 V..750V |
290 V..750 V |
370 V..750 V |
430 V..750 V |
280 V..750 V |
320 V..750 V |
Minimum voltage for rated power |
250 V |
250 V |
250 V |
250 V |
250 V |
250 V |
250 V |
Maximum DC voltage |
900 V |
900 V |
900 V |
900 V |
900 V |
900 V |
900 V |
Maximum DC current |
1 x 9 A /
1 x 9 A |
1 x 18 A /
1 x 9 A |
2 x 18 A |
2 x 18 A |
2 x 18 A |
3 x 16 A |
3 x 16 A |
Number of MPP-Trackers |
2 |
2 |
2 |
2 |
2 |
3 |
3 |
Max. PV generator
output per MPP
tracker
|
5 000
W |
MPPT1:
9 000 W
MPPT2:
5000 W |
9
000 W |
9
000 W |
9
000 W |
9
000 W |
9
000 W |
String connections |
1 x 2 / 1 x 1 |
1 x 2 / 1 x 1 |
2 x 2 |
2 x 2 |
2 x 2 |
3 x 2 |
3 x 2 |
Connection type |
MC 4 |
MC 4 |
MC 4 |
MC 4 |
MC 4 |
MC 4 |
MC 4 |
Output values |
Rated output power at cos(φ) = 1 |
6 000 W |
8 000 W |
10 000 W |
13 000 W |
15 000 W |
13 000 W |
15 000 W |
Maximum apparent
output power
|
6 000 VA |
8 000 VA |
10 000 VA |
13 000 VA |
15 000 VA |
13 000 VA |
15 000 VA |
Nominal mains
voltage
|
3 x 400 V |
3 x 400 V |
3 x 400 V |
3 x 400 V |
3 x 400 V |
3 x 400 V |
3 x 400 V |
Maximum AC current |
3 x 9 A |
3 x 12 A |
3 x 16 A |
3 x 20 A |
3 x 22 A |
3 x 20 A |
3 x 22 A |
Mains nominal
frequency / range
|
50 Hz / 45 Hz…55 Hz |
Power factor cos(φ) |
Adjustable from 0.8 overexcited to 0.8 underexcited |
Distortion factor at
rated power
|
< 3 % |
Connection type |
Connector (locking) |
Grid connection |
Three-phase (L1 / L2 / L3 / N / PE) |
Power input at night |
0 W |
Efficiency |
Max. efficiency |
98.0 % |
Europ. efficiency |
97.5 % |
Power input |
Own consumption (night) |
0 W |
Ambient conditions |
Protection type |
IP65 |
Ambient temperature
range for rated
power output
|
-20 °C…+60 °C (+50 °C) |
Relative humidity |
0…98 % (no condensation) |
Maximum altitude
above sea level
|
2000m (without derating) |
Noise emissions (↔
1.5 m) |
51 dB(A) fan off / 58 dB(A) fan on |
Configuration |
Display |
Graphic LC display with backlight and status LED |
Circuit type |
Two-stage, transformerless |
Data logger |
Data logger for energy yield, peak output, and operating duration for
the last 31 days,
12 months, and 10 years
|
Fault current
monitoring |
Internal, AC/DC sensitive |
Casing |
Aluminium |
Overvoltage
conductor DC |
Requirement class C (VDE 0675-6) and/or type 2 (EN 61643-11) |
Overvoltage
conductor AC |
Requirement class D (VDE 0675-6) and/or type 3 (EN 61643-11) |
Standards & guidelines |
CE-compliant |
Yes |
EMC |
EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11 / EN 61000-3-12 / EN
61000-6-2 /
EN 61000-6-3 |
Grid connection 2) |
VDE-AR-N 4105 / VDE 0126-1-1 A1:2012 / BDEW MS-Richtlinie / CEI 0-21 /
CEI 0-16
/ RD 661 / RD 1699 / G59/2 / G83/2 / PPC Guide / C10/11 / EN
50438 / AS 4777 |
Device safety |
IEC 62109-1/-2 |
Interfaces |
Data communication |
RS485 / Ethernet |
Status signalling contact |
M12 connector with relay as N/C contact / N/O contact |
Connection of
external grid
monitoring |
M12 connector |
Weight & dimensions |
Weight |
34 kg |
37 kg |
39 kg |
39 kg |
39 kg |
42 kg |
42 kg |
Dimensions in mm (W x H x D) |
550 x 750 x 200 |
Warranty |
Warranty |
Standard 5 years / extension to 10, 15, 20 or 25 years
possible |