SolarMax 2000P |
SolarMax 3000P |
SolarMax 4000P |
SolarMax 4600P |
SolarMax 5000P |
Цени |
Запитване |
Запитване |
Запитване |
Запитване |
Запитване |
Input values |
MPP voltage range 1) |
210 .. 480 V |
310 .. 480 V |
210 .. 480 V |
240 .. 480 V |
260..480 V |
Minimum DC voltage |
120 V |
120 V |
120 V |
120 V |
120 V |
Maximum DC voltage |
600 V |
600 V |
600 V |
600 V |
600 V |
Maximum DC current |
10 A |
10 A |
10 + 10 A |
10 + 10 A |
10 + 10 A |
Number of MPP trackers |
1 |
1 |
2 |
2 |
2 |
Number of string connections |
1 |
1 |
2 |
2 |
2 |
Connection type |
Wieland PST40i1 (MC4 identical in design) |
Output values |
Rated output power 2) |
2 000 W |
3 000 W |
4 000 W |
4 600 W |
5 000 W |
Maximum apparent output power 2) |
2 000 VA |
3 000 VA |
4 000 VA |
4 600 W |
5 000 VA |
Maximum AC current |
9 A |
13.5 A |
17.5 A |
22 A |
22 A |
Nominal mains voltage / range |
230 V / 184 .. 276 V |
Mains nominal frequency / range |
50 Hz / 45 Hz…55 Hz |
Power factor cos(φ) |
Adjustable from 0.8 overexcited to 0.8 underexcited |
Distortion factor at rated output power |
< 3 % |
Connection type |
Terminal (2.5 – 10 mm2) |
Grid connection |
One-phase (1 / N / PE) |
Power input at night |
0W |
Efficiency |
Max. efficiency |
97.5 % |
97.5 % |
98.0 % |
98.0 % |
98.0 % |
Europ. efficiency |
97.0 % |
97.0 % |
97.5 % |
97.5 % |
97.5 % |
Ambient conditions |
Protection type |
IP65 |
Ambient temperature range (for rated power output) |
-20 °C…+60 °C |
Relative humidity |
0…100% (condensation) |
Max. operating level above sea level |
2000m (without derating) |
Fire protection class |
V0 |
Noise emissions |
< 30 dB(A) (↔ 1.5 m) |
Configuration |
Display |
Graphic LC display with backlighting and status LED |
Inverter topology |
HERIC®, transformerless |
DC disconnector |
Integrated |
Data logger |
Energy yield, peak output and operating hours of the last 31 days, 12
months, 10 years.
Performance curves of the last 7 days. |
Fault current monitoring |
Internal, AC/DC sensitive |
Housing / service cover |
Aluminium / plastic ASA+PC |
Surge protection DC and AC |
Requirement class D (VDE 0675-6) and/or type 3 (EN 61643-11) |
Standards & guidelines |
CE-compliant |
Yes |
EMC |
EN 61000-3-2 / EN 61000-3-3 / EN 61000-3-11
/ EN 61000-3-12 / EN 61000-6-2 /
EN 61000-6-3 |
Standard / guideline compliance |
VDE 0126-1-1 / VDE-AR-N 4105 / CEI 0-21 3) / RD 661 /
RD 1699 / G83/2 / G59/2 / PPC Guide / C10/11 / EN 50438 4) |
Grid connection |
VDE 0126-1-1 A1:2012 / VDE-AR-N 41053)/ CEI 0-21 / RD 661 / RD 1699 / G83/2 /
G59/2 / PPC Guide / C10/11 / EN 50438 |
Device safety |
IEC/ EN 62109-1/ -2 |
Interfaces |
Data communication |
RS485 / Ethernet (Plug&Play) |
Status signalling contact |
With optional I/O module |
Connection ripple control signal receiver |
Connection of external lightning protection control |
Connection external grid monitoring |
Connection of external energy meter |
Weight & dimensions |
Weight |
17 kg |
17 kg |
19 kg |
19 kg |
19 kg |
Dimensions in mm (W x H x D) |
476 x 360 x 180mm |
Warranty |
Warranty |
Standard 5 years / extension to 10, 15, 20, or 25 years possible |